Forward / reverse motor control with a PLC
Reversing a 3-phase motor means swapping two phases with a second contactor. If both contactors ever pull in together, two phases are shorted. That is why every forward / reverse circuit is built around an interlock.
How reversing works
A 3-phase motor turns the other way when any two of its three phases are swapped. The forward contactor KM1 connects L1-L2-L3 to U-V-W; the reverse contactor KM2 connects them as L3-L2-L1. Both feed the motor through one overload relay. See contactors and overloads.
Inputs and outputs
| Signal | Device | Siemens-style address |
|---|---|---|
| FWD | push button NO | I0.0 |
| REV | push button NO | I0.1 |
| STOP | push button NC | I0.2 |
| OL | overload NC contact 95-96 | I0.3 |
| KM1 | forward contactor coil | Q0.0 |
| KM2 | reverse contactor coil | Q0.1 |
The ladder logic
|--+--[ FWD ]--+--[ STOP ]--[ OL ]--[/REV ]--[/KM2 ]--( KM1 )--| | +--[ KM1 ]--+ |--+--[ REV ]--+--[ STOP ]--[ OL ]--[/FWD ]--[/KM1 ]--( KM2 )--| | +--[ KM2 ]--+
- Each direction has its own seal-in.
[/KM2]in the forward rung and[/KM1]in the reverse rung: the output interlock. While one runs, the other cannot start.[/REV]and[/FWD]: the push-button interlock. Pressing both buttons starts neither.
Always add a hardware interlock
The software interlock is not enough on its own: a contactor can weld, or an output can fail on. Wire an auxiliary NC contact of KM2 in series with the KM1 coil and vice versa, and use a mechanically interlocked contactor pair where possible. The PLC interlock and the hardware interlock protect against different failures; real panels use both.
A delay before changing direction
Reversing a motor that is still spinning causes a huge current and mechanical shock. Add an off-delay or require the motor to stop first:
|--[/KM1 ]--[/KM2 ]--------( TON T0, 2 s )--| both off for 2 s | ...and add [ T0 ] in series in both start rungs
With a VFD instead of contactors
A variable frequency drive reverses electronically: the PLC simply switches the drive's FWD or REV input, and the drive ramps down and up again. The same interlock idea still applies in the program, so the PLC never asks for both directions at once.
Watch it on the PLC Sim Lab channel
Watch the interlock block the reverse contactor while forward is running. Open on YouTube → · More videos →
Try it yourself. Wire sensors, contactors and a PLC, write ladder logic and press RUN in the free PLC Sim Lab Playground. Nothing to install.
Open the Playground →Guided lessons →Frequently asked questions
How do you reverse a 3-phase motor?
Swap any two of the three phases, normally with a second contactor (or by commanding reverse on a VFD).
What is an interlock in forward reverse control?
A normally closed contact of each contactor in the other direction circuit, so the forward and reverse contactors can never be on at the same time. Use it both in the PLC program and in the hardware wiring.
Why add a delay when changing direction?
To let the motor stop before it is reversed. Plugging a spinning motor into the opposite direction draws a very high current and stresses the mechanics.