Starting a large induction motor directly on-line draws 6 to 8 times its rated current, which dips the supply voltage and stresses the machine. A star-delta starter starts the motor with reduced voltage on each winding, then switches to full voltage once it is up to speed.

3 min read · Updated 2026-10-02

Star and delta connections

A 3-phase motor has three windings, with six terminals: U1-U2, V1-V2, W1-W2.

In star, each winding has √3 times less voltage, so the line current and the starting torque are both about one third of a direct delta start.

The three contactors

ContactorFunctionClosed during
KM1 (main / line)feeds L1, L2, L3 to U1, V1, W1star and delta
KM3 (star)shorts U2, V2, W2 togetherstar only
KM2 (delta)connects U2, V2, W2 to the lines (making the ring)delta only

The sequence

  1. START: KM3 (star) and KM1 (main) close. The motor accelerates in star.
  2. After the star time (typically 5–15 s, when the motor is near full speed) KM3 opens.
  3. After a short pause (30–80 ms) KM2 (delta) closes. The motor runs in delta at full power.
  4. STOP: KM1 and KM2 open.

The pause ensures the star contactor's arc is out before delta closes. KM2 and KM3 must never be closed together: that would short-circuit the supply. They are interlocked twice: mechanically and with each other's NC auxiliary contacts in the coil circuits, and also in the PLC program.

PLC program (simplified)

Run      := (Start OR Run) AND Stop_OK AND OL_OK
KM1      := Run
KT_star  := TON(IN := Run, PT := 8 s)
KM3      := Run AND NOT KT_star.Q AND NOT KM2_fb
KT_pause := TON(IN := KT_star.Q, PT := 60 ms)
KM2      := Run AND KT_pause.Q AND NOT KM3_fb

See PLC timers and ladder logic.

Overload setting

When the overload relay sits after KM1 in the line to U1/V1/W1, it carries the winding (phase) current, which in delta is the line current ÷ √3. So set it to 0.58 × the motor's rated current. If it is placed in the incoming supply, set it to the full rated current.

Which motors can be started star-delta?

The motor must be designed to run in delta at your supply voltage. On a 400 V supply you need a motor marked 400 V Δ / 690 V Y. A 230 V Δ / 400 V Y motor runs in star on 400 V and cannot use star-delta. Also, the load must allow a low starting torque: fans and pumps are fine; a fully loaded conveyor may not accelerate in star.

Drawbacks and alternatives