PLC Sim Lab
Ladder logic how-tos

PLC troubleshooting checklist

When a machine stops, the fastest technicians are not the ones who know the program best, but the ones who check things in the right order. Use this checklist from the outside in: power, PLC, inputs, outputs, wiring, and only then the program.

3 min read · Updated 2026-10-02

1. Ask what happened

The operator's answer often points straight at the faulty area.

2. Power and protection

3. The PLC itself

4. Inputs: does the PLC see the sensor?

Operate the device by hand (press the button, put metal in front of the sensor) and watch the input LED. Then check the bit online in the program.

Input LEDMeaningCheck next
Off, device operatedno signal reaches the inputsensor supply, sensor LED, wiring, PNP / NPN vs input common
On, bit stays 0wrong address or input module faultaddress in the program, module diagnostics
On all the timesensor stuck, short to +24 V, wrong NO/NCdisconnect the wire and watch the LED

A sensor's own LED on but the PLC input off is the classic PNP / NPN or sinking / sourcing mismatch.

5. Outputs: does the load get power?

6. Wiring with a multimeter

Measure voltage against 0 V step by step from the supply to the device: +24 V should be present up to the open point in the circuit. For an NC safety chain (E-stops, guard switches), the point where 24 V disappears is right after the open contact. Never check continuity on a live circuit. See PLC wiring basics.

7. Only now: the program

The ten most common causes

  1. Sensor misaligned, dirty or damaged
  2. Broken wire or loose terminal
  3. Tripped overload or breaker
  4. Emergency stop or guard circuit open
  5. Blown fuse on an output group
  6. Faulty contactor coil or relay
  7. PNP / NPN sensor replaced with the wrong type
  8. Air pressure low (pneumatic machines)
  9. PLC in STOP after a power dip or a download
  10. A program change nobody documented

Practise fault finding safely

The PLC troubleshooting challenges give you 12 machines, each with one hidden fault, an operator complaint and a multimeter. You fix them in the simulator, and they count towards the free certificate.

Watch it on the PLC Sim Lab channel

A real fault-finding example: why a pump system fails, how to find it and how to fix the ladder. Open on YouTube → · More videos →

Try it yourself. Wire sensors, contactors and a PLC, write ladder logic and press RUN in the free PLC Sim Lab Playground. Nothing to install.

Open the Playground →Guided lessons →

Frequently asked questions

What is the first thing to check when a PLC machine stops?

Power and safety: the 24 V supply at the PLC, tripped breakers, the emergency stop and guard circuits, then whether the PLC is in RUN without errors.

How do I know if a PLC input is faulty?

Operate the device and watch the input LED. If the sensor works but the LED stays off, measure the signal at the input terminal; voltage present with no LED points to the input or its common, no voltage to the sensor or wiring.

Should I look at the PLC program first?

No. Most faults are in field devices and wiring. Check power, the PLC status, inputs and outputs first, then follow the rung of the output that does not work.