PLC troubleshooting checklist
When a machine stops, the fastest technicians are not the ones who know the program best, but the ones who check things in the right order. Use this checklist from the outside in: power, PLC, inputs, outputs, wiring, and only then the program.
1. Ask what happened
- What exactly does not work, and what still works?
- Did it stop suddenly, or has it been getting worse?
- Was anything changed: a part replaced, a program downloaded, a setting adjusted?
- Are there alarms on the HMI, and in what order did they appear?
The operator's answer often points straight at the faulty area.
2. Power and protection
- Is the 24 V DC supply present? Measure it at the PLC terminals, not only at the power supply.
- Any tripped circuit breakers, blown fuses, or a power supply in overload (LED flashing)?
- Is the emergency stop circuit reset, guard doors closed, the safety relay showing OK?
3. The PLC itself
- Is it in RUN? A PLC in STOP leaves every output off.
- Any error / fault LED? Read the diagnostic buffer with the programming software.
- Communication: are remote I/O stations and drives online?
4. Inputs: does the PLC see the sensor?
Operate the device by hand (press the button, put metal in front of the sensor) and watch the input LED. Then check the bit online in the program.
| Input LED | Meaning | Check next |
|---|---|---|
| Off, device operated | no signal reaches the input | sensor supply, sensor LED, wiring, PNP / NPN vs input common |
| On, bit stays 0 | wrong address or input module fault | address in the program, module diagnostics |
| On all the time | sensor stuck, short to +24 V, wrong NO/NC | disconnect the wire and watch the LED |
A sensor's own LED on but the PLC input off is the classic PNP / NPN or sinking / sourcing mismatch.
5. Outputs: does the load get power?
- Is the output bit on in the program, and is the output LED on?
- Bit on, LED off: the output is forced off, or the output module / its supply has a fault.
- LED on, device not working: measure the voltage at the device. Voltage present: the device is faulty. No voltage: broken wire, open terminal, or a missing return to 0 V.
- Outputs driving contactors: check the contactor coil and its overload.
6. Wiring with a multimeter
Measure voltage against 0 V step by step from the supply to the device: +24 V should be present up to the open point in the circuit. For an NC safety chain (E-stops, guard switches), the point where 24 V disappears is right after the open contact. Never check continuity on a live circuit. See PLC wiring basics.
7. Only now: the program
- Go online and follow the rung that drives the output that does not work. Which contact is not passing power?
- Look for forced bits, a timer whose preset was changed, a counter that was never reset.
- Is the same output written in two places (double coil)? The last rung wins.
- Was the program in the PLC changed? Compare it with the backup.
The ten most common causes
- Sensor misaligned, dirty or damaged
- Broken wire or loose terminal
- Tripped overload or breaker
- Emergency stop or guard circuit open
- Blown fuse on an output group
- Faulty contactor coil or relay
- PNP / NPN sensor replaced with the wrong type
- Air pressure low (pneumatic machines)
- PLC in STOP after a power dip or a download
- A program change nobody documented
Practise fault finding safely
The PLC troubleshooting challenges give you 12 machines, each with one hidden fault, an operator complaint and a multimeter. You fix them in the simulator, and they count towards the free certificate.
Watch it on the PLC Sim Lab channel
A real fault-finding example: why a pump system fails, how to find it and how to fix the ladder. Open on YouTube → · More videos →
Try it yourself. Wire sensors, contactors and a PLC, write ladder logic and press RUN in the free PLC Sim Lab Playground. Nothing to install.
Open the Playground →Guided lessons →Frequently asked questions
What is the first thing to check when a PLC machine stops?
Power and safety: the 24 V supply at the PLC, tripped breakers, the emergency stop and guard circuits, then whether the PLC is in RUN without errors.
How do I know if a PLC input is faulty?
Operate the device and watch the input LED. If the sensor works but the LED stays off, measure the signal at the input terminal; voltage present with no LED points to the input or its common, no voltage to the sensor or wiring.
Should I look at the PLC program first?
No. Most faults are in field devices and wiring. Check power, the PLC status, inputs and outputs first, then follow the rung of the output that does not work.